PadPuls M2
The 2-channel pulse adaptor PadPuls M2 allows the use of up to 2 meters with pulse output as M -Bus slaves.
- Two separated pulse inputs
- Safe detection of up to 15 pulses per second at each input
- Pulse debouncing
- Pulse value free adjustable
- Plug-in terminals simplify the installation wiring
- Unit free selectable (e.g. Wh, kWh, MWh, kJ, m3, l,...)
- Counter length: 8 decimal digits
- Due-date function with integrated realtime clock
- One yearly value and 15 monthly values (optional)
- M-Bus protocol according to EN13757-2 and -3
- Fully parameterizable by M-Bus, including overwrite protection
- Transmission rate: 300 and 2400 baud with auto baud detection
- Fully operable in case of M-Bus failure by integrated battery
- Case for wall mounting W x H x D: 80 x 80 x 52 mm
- Two battery options available
- Protective class IP 54 (IP65 is possible)
The devices of the PadPuls M2 series adapt up to two conventional meters with pulse output to a M-Bus system. The two counter inputs are nearly free parameterizable and fit in already existing installations.
Optionally the user can activate a tariff function, by which energy or volume pulses can be accumulated in separate meter readings for primary and secondary tariffs. O one pulse signal and one changeover signal for the tariff are required, for example out of a ripple control receiver from the electricity supplier.
The integrated battery ensures that the impulse adaptor is fully operable, even if the M-Bus network fails. Additional security is provided by the periodic saving of the meter readings in nonvolatile memory.
Technical Data
Power supply | Remote supply by M-Bus with automatic switch to battery on bus fail |
Bus operation | max. 1.5mA (1 unit load), no load of battery |
Battery operation | Current draw typ. 8μA |
Battery lifetime 0,23Ah | 10 years at max. 80 failure days p.a. (changeable coin type battery) |
Batterie lifetime 1,80Ah | 10 years at max. 250 failure days p.a. |
Operating temperature | 0..55 °C |
Pulse inputs | 2, individually programmable |
Contact voltage | 2,5V .. 3,6V |
Contact current | 30μA |
Debouncing time | 5ms |
Cable pulse generator | max. 10m |
Requirements to contacts of pulse generators | |
Potential | free of potential |
Resistance | open > 1MΩ, closed < 2kΩ |
Contakt duration, - pasue | min. 30ms |
Pulse frequency | max. 14 Hz |
Tariff signal | potential free (data see above) |
M-Bus protocol | according to EN13757-2 and -3 |
Baudrates | 300, 2400 and 9600 baud (automatic detection) |
Mounting | Wall mounitng |
Protective class | IP54 (IP65 possible) |
Dimensions | WxHxD:80x80x52mm |
Downloads
- Manual PadPuls M2IM003G_E.pdf
- Description of changes (redesign)REDESIGN_PADPULSM2.pdf
- FlyerFlyer_PadPulsM2VEngF.pdf
Ordering information
Order Number | Description |
---|---|
IM003G | PadPuls M2 |
Both versions including configuration software MBCONF