PadPuls M2W
The PadPuls M2W is a 2-channel pulse to Wireless M-Bus adaptor. The battery driven PadPuls M2W sends the data according to the OMS standard.
- Wireless M-Bus according to standard EN 13757-4 Mode S, T and C
- OMS conform and compatible (Spec 4.X.X)
- Optional encryption Mode 5 or 7, AES
- Two seperated pulse inputs (for reed contacts, optocouplers,...)
- Save detection of up to 18 pulses per second on both inputs
- Debouncing
- Free adjustable pulse value
- Free choice of units (e.g. Wh, kWh, MWh, kJ, m3, l,...)
- Configuration via USB-converter cable (NOT INCLUDED)
- Transmission interval adjustable between 10 seconds and 2 hours
- Battery supplied
- Battery lifetime about 14 years at 15min transmitting
- Distributionbox for wallmounting
The PadPuls M2W is used for the wireless integration of up to two conventional consumption meters with pulse outputs into a wireless M-Bus radio system. The two count inputs can be parametrized almost arbitrarily via an adapter cable and can be adapted to existing installations. With the PadPuls M2W meter readings of water, gas, electricity and heat meters, which do not have a communication interface, can easily be transmitted to a wireless M-Bus receiver. For integration into an existing wired M-Bus system, our Wireless M-Bus to M-Bus gateway RelAir R2M can be used.
Technical Data
Standard | EN13757-4 and EN13757-3, OMS compatible |
Transmission mode | S1,T1,C1 (unidirectional) / Frame Format A |
Encryption | Mode 0 (no encryption), Mode 5 or Mode 7 |
Transmission interval | Programable: 10 Seconds to 2 hours |
Battery lifetime (2400 mAh, fixly soldered, not changeable) | Transmission interval 15 min. / 2 channels / T-Mode: about 14 years |
Pulse inputs | 2, individually programable |
Contact voltage | 2,5V .. 3,6V |
Contact current | 30μA |
Debouncing time | 5ms |
Cable pulse generator | max. 10m |
Requirements to contacts of pulse generator | |
Potential | potential free |
Resistance | open > 1MΩ, closed < 2kΩ |
Contact duration, -pause | min. 30ms |
Pulsfrequency | max. 18 Hz |
Mounting | Wall mounted |
Protection class | IP54 (up to IP65 possible) |
Dimensions | W x H x D: 80 x 80 x 52 mm |
Temperature range | 0 to 40°C |
Downloads
- Flyer PadPuls M2WFlyer_PadPuls_M2W_01-2017.pdf
- User manual PadPuls M2WUser_Manual_IM003GW.pdf
- Configuration software MBConfMBConf_Setup1.exe
- Virtual comport driver for programming cableCDM_v2.12.28_WHQL_Certified.zip
- User manual USB to UART cableDS_TTL-232R_CABLES.pdf
Ordering information
Order Number | Description |
---|---|
IM003GW | PadPuls M2W Wireless M-Bus Pulse adapter for 2 channels |
KV003 | USB to UART programming cable |